Tuesday, 24 October 2017

Challenging designs

Sir Sean Connery, most famous for his award-winning portrayal of James Bond, once said “there is nothing like a challenge to bring out the best in man.” These are wise words as we all continually face our own challenges, throughout every aspect of life. 

Here, Ian McWha, key account manager at industrial systems integrator Boulting Technology, explores the importance of recognising and overcoming challenges when designing a switchboard. 

When plant managers look to install a new switchboard in their facility, they are often presented with a range of challenges that they must address. Identifying these challenges as soon as possible is imperative to the success of the installation and the functionality of the switchboard. If not addressed, these issues can have drastic consequences, causing production downtime or even damage to other systems and employees.  

Design challenges
Each facility is unique and as such will have its own design requirements, dependant on the function of the plant. 

Many plants have limited space that they are keen to maximise, so the footprint of the switchboard needs to be as small as possible, while ensuring its integrity is not compromised.

Boulting Technology’s designers are experienced in creating bespoke systems that meet client specifications, particularly in space-short environments. Bespoke MCC designs include, integrated back to back systems with shared riser and main distribution bars, custom made U shape centres, L shape units that fit round corners and bridges that extend above equipment and wall partitions. 

The specific needs of each job may also present additional challenges that the design engineer must be aware of. When working with pumping stations for example, a switchboard may be required to be near water. In these cases, the ingress protection (IP) rating, which classifies the degrees of protection provided against solid objects, dust, and water must be adhered to. 

As challenges are often individual to a facility, a unique switchboard may be the answer. Bespoke solutions such as Boulting Technology’s can make the most of limited space or other restrictions, while meeting client specifications exactly. 

Maintenance 
Forward planning is essential when installing new equipment, especially when establishing a regular maintenance programme. Planned and predictive maintenance is crucial to keep machinery working efficiently for as long as possible, avoiding production downtime. To solve this, plant managers should work closely with the switchboard manufacturer to develop a robust maintenance programme. 

Boulting Technology offers an all-encompassing maintenance solution, which includes a comprehensive survey that assesses control systems across a facility. An initial online survey assesses areas, such as obsolete parts, equipment life cycle and efficiency. 

From the survey, a series of multi stage recommendations provide a hierarchy of risk, allowing plat managers to focus on high risk critical systems in the first instance and implement an appropriate plan of action. 

Safety
Not properly addressing design challenges can cause safety issues. For example, it is essential that the switchboard has the correct rated short time withstand rating. This is the rating of current that the assembly can withstand for a set period of time without the aid of a short circuit protective device (SCPD). The short time withstand rating, used by engineers to determine the ability of the assembly to protect itself and other devices, is made up of two parts: the fault current rating in kiloampere (kA) and the duration time.

Manufacturers also need to be aware of the prospective short circuit current (PSCC) or fault current. The PSCC is the highest electric current which can exist in a system under short-circuit conditions. 

While engineers should always be aware of the PSCC, specific applications such as when operating transformers in parallel, can present dangerous situations if not managed correctly. 

Legislation, such as BS EN 61439 is the first step to ensuring switchboard safety. BS EN 61439 is a mandatory standard for all low voltage switchboard assemblies (LVSAs) and helps the manufacturer and plant manager ensure the board achieves acceptable levels of performance, safety and reliability. 

It is important to choose a manufacturer and integrator which understands the relevant legislation, how to meet them and how to ensure the product is safe, while also meeting customer requests and requirements. 

While meeting legislation standards is important, it does not automatically mean the switchboard is fit for the desired purpose. Safety requirements can easily be met without the equipment meeting client specifications or even working correctly. Legislation should be one of many considerations when installing new equipment.  

Thinking outside of the box means design challenges can not only be overcome, but can become useful, resulting in bespoke ideas and revolutionary products. This is just as true for engineers designing industrial products such as low voltage switchboards, as it has been throughout the brilliant Sean Connery’s life. 

Wednesday, 2 December 2015

From switchroom to container

A 20 metre container could accommodate approximately 2,000 cases of wine, a small cafe or your company’s next switchroom. Industrial sectors are taking advantage of this versatility, and containerised electrical switchrooms are becoming a common sight. Here, Nick Boughton, sales manager at Boulting Technology, explains why the answer to complex electrical projects isn’t always adapting the system to fit the space.

Traditionally, systems integrators faced with a project would build the equipment in-house, transport it to site and spend time installing and testing it. Although this sounds like a relatively straightforward process, the reality is much more complex and there are plenty of opportunities for logistic difficulties to rear their ugly heads.

Safe transport is always tricky, especially when your “passenger” weighs a few tonnes and remote locations can be difficult to reach, particularly when there are only dirt roads going your way. Once on site, the equipment itself – usually large power distribution boards or motor control centres (MCCs) - can be difficult to get to wherever the switchroom is tucked away. Additional health and safety measures also need to be taken if there are people working in the building.

Fortunately, there is an easier way. By using an industrial container to host the switchroom and building all the equipment, lighting, cabling and HVAC into the room, companies can avoid most of these logistic headaches altogether. The project is always client-led and containerised switchrooms are highly customisable, which means the approach can reconcile even some of the toughest requirements in industry.

Controlled environment
The main advantage of containerisation is its controlled environment. It’s easier to plan, design, implement, test and especially maintain a containerised switchroom, as long as the right monitoring is in place.

Temperature is one of the most complex things to manage in any switchroom, especially when the space doesn’t allow natural air flow. With a container, it’s easy to install the necessary HVAC equipment in the initial stage of the project, along with remote temperature monitoring and alarms, which allow control engineers to identify a deviation from the normal parameters long before it becomes a risk.

For larger or more complex projects, the container approach also means better scalability, because as long as the client allows for some space next to the original container, it’s easy to get another one commissioned, designed and delivered.

Overall, the time it takes to design and test a containerised switchroom is significantly shorter than a more traditional approach that fits a system to a room. It’s faster and easier for the client, contractor and any third parties to fit all the requirements in a separate, controlled environment that can be delivered to the site, plugged in and left to run.

While it’s true that the capital cost of a containerised switchroom can be higher than a traditional system, this approach usually results in lower overall project costs, because it reduces testing and even building times significantly.

Remote or difficult sites
The containerisation approach works particularly well for remote environments, such as substations located in the middle of nowhere. The reverse is also true. In busy locations or areas of high risk or high security, it’s much easier to fit and test a switchroom when it comes neatly wrapped up in a “box” that doesn’t need any unwrapping. In nuclear projects, for example, where security, regulations and radiation can be significant hindrances for contractors a kitted out container is the easiest, fastest and most reliable bet.

A recent project saw Boulting Technology design, build and install a 20m containerised electrical control room for a nuclear site. The container housed power distribution, MCCs, control panel suites and stand-alone control panels. Boulting Technology built the MCCs and control panels in its Warrington factory, integrated them into a prefabricated container at the company’s St Helens mechanical workshop and completed the electrical fit out, installation and testing even before the container reached the site.

No more headaches
2,000 cases of wine would lead to one hell of a headache (to drink or to transport!), but containerised switchrooms are exactly the opposite. They reduce the ov
erall project timescale and logistic difficulties and they can be built exactly to the requirements of a client. Boulting Technology has yet to come across a project it couldn’t tackle, so if you’re stuck with a U-shaped switchroom with very small doors, don’t worry – a container switchroom might be just the thing you’re looking for.

To find out more, get in touch with Boulting Technology on +44 1925 720 090 or visit the Boulting Technology website on www.boultingtechnology.co.uk.

Tuesday, 10 November 2015

Choosing the right critical power supply

Today, more than 3 billion people live in cities and the urban population of the planet increasing constantly. This means a growing demand for electrical power and more complex requirements for buildings and manufacturing facilities. Add strict energy standards to the equation and the process of identifying the right critical power supply for individual applications becomes exceedingly tricky. Here, Pat McLaughlin, Boulting Technology’s Operations Director, discusses what companies should keep in mind when choosing a switchboard.

Fault capacity and ruggedness
Before commissioning a low voltage switchboard, consider what kind of external fault you can expect to have in the application. Usually this means choosing a fault rating higher than the maximum supply capacity. The rule of thumb is: fault rating = (transformer VA /700) * 20. This way, your system should be safe even in the event of an external fault.

Boulting Power Centre
Another thing to consider is the product’s lifespan. Switchboards generally have relatively long lives and can last anywhere between 25 and 40 years, perhaps even more if you treat them right and ensure the regular maintenance they deserve. However, this also means they need to be rugged and durable, so they can withstand the occasional knock and abuse life throws their way.

Location and security
Industry has a tendency to leave the electrical room layout to the very end of the building design and adapt it to suit whatever space is left over. Try to avoid this approach if you can.

Ideally, you want your electrical room to be spacious and well ventilated. If possible, there should be enough space to allow repair and replacement work to take place as smoothly as possible. Switchboards are only installed once, but there’s a good chance you will need to add cables or modules as time goes by. Devices may have shrunk, but the laws of physics and the size of cables haven’t changed.

Access to your building’s power centre boards should only be granted to authorised personnel, rather than allowing just anyone to walk in and out. Ideally, the switchboard should be located in a secured room, out of the way, so visitors don’t just stumble in while looking for the rest rooms. In addition, electrical gear is a tempting target for thieves, so it’s important to protect it accordingly from malicious attacks or vandalism.

Futureproofing
Because of their long lifespan, switchboards should be designed to last a few decades. One way of future proofing a low voltage assembly is by using a modular design. There’s a chance that as you grow, you will require more capacity. You can easily achieve this by putting a bus coupler on the end, so you can extend and modify the switchboard without shutdown. Modularity also means that if a section of the power centre breaks down it can be easily replaced without having to turn off the whole thing.

Speaking of growth, another thing you might need if you want your switchboard to be future proof is a few spare distribution and motor control feeders. They might add to the final cost, but they might also be a lifesaver a few years down the line. You can’t predict the future, but you can make it easier for those who follow you.

Keeping it simple
To make sure sources can’t be cross-connected, even if the electrical control fails, all the switches should be mechanically interlocked. Interlocking switchgear ensures personnel are safe and equipment is operated according to the correct procedures.

Labelling in large switchboards can be very confusing, so colour coding is a good way of keeping track of supplies. Sometimes special symbols can also be used for multiple sources of supply, but colour coding is the simplest and best method. It offers an ‘at a glance’ view of the system and minimises the risks of mistakes.

Very few switchboards these days will operate critical processes manually, so remote signalling and switching is something you should consider when choosing a switchboard. It’s important to make sure that if the main power goes down in the middle of the night, or over the weekend, the generator needs to be on and fully functional.

Testing
Speaking of generators, you need to ensure that you test them regularly using a load bank. You should design the switchboard in such a way that testing is easy; otherwise excuses will appear and testing will be delayed. Make sure this doesn’t happen and you won’t be left in the dark when the power goes out. Switchboards need constant attention to always be at the top of their game.

These are just some of the main things to consider when deciding the requirements for low voltage switchboards. It can be a difficult process, but luckily help is never too far away. To find out more about what options are available for your low voltage assembly, get in touch with Boulting Technology on +44 1925 720 090.

Friday, 2 October 2015

Changing industry standards: one year on

Boulting Technology - Systems integration - BS EN 61439
Pat McLaughlin
In 1998, Google was founded, the first Apple iMac was introduced and the legendary Windows ’98 was released by Microsoft. In a less glamorous but equally important corner of industry, a new commission was being formed to revise the complex IEC 60439 industry standard, which governed the safety and performance of electrical switchgear assemblies. Although Windows ‘98 has long been consigned to history, the new industry standard – BS EN 61439 – only became mandatory on November 1, 2014. 

One year on, Pat McLaughlin, Boulting Technology’s Operations Director, evaluates how original equipment manufacturers, panel builders, electrical engineers, consulting engineers and contractors have been affected by the new BS EN 61439 standard.

Why a new standard?
In a market where the demand to optimise and reduce costs blends heavily with higher needs for assembly flexibility, the introduction of a new set of standards was needed to  guarantee the performance of Low Voltage Switchgear Assemblies.

Switchgear and Control Gear assemblies are multifaceted and have an endless number of component combinations. Before the introduction of the new standard, testing every conceivable variant was not only time consuming and costly, but impractical.

The intricate character of assemblies also meant that many did not fit into the previous two testing categories: Type Tested Assembly (TTA) and Partially Tested Assembly (PTTA). For example, panels which were too small to be covered by TTA and PTTA fell outside the standard. Finally, in the case of a PTTA, ensuring the safety and suitability of a design was often dependent strictly on the expertise and integrity of the manufacturer.

Design verification
Boulting Technology - Systems integration - BS EN 61439
The Boulting Power Centre
The major change introduced by the new BS EN 61439 standard refers to testing. It states that the capabilities of each assembly will be verified in two stages: design verification and routine verification. This means the new standard completely discards the type-tested (TTA) and partially type-tested assemblies (PTTA) categories in favour of design verification.

Although BS EN 61439 still regards type testing as the preferred option for verifying designs, it also introduces a series of alternative routes to design verification.

The options include using an already verified design for reference, calculation and interpolation. The BS EN 61439 standard specifies that specific margins must be added to the design, when using anything other than type testing.

One of the main benefits of the new design verification procedure is its flexibility. Under the old BS EN 60439 specification customers would demand a Type Test certificate for each assembly particularly Incoming Air Circuit Breakers, which was very expensive and time consuming.

The new standard allows users and specifiers to pertinently define the requirements of each application. Annex D of the BS EN 61439 standard provides a list of 13 categories or verifications required, what testing method can be used and what comparisons can be made. In order to optimise testing time, the standard allows derivation of the rating of similar variants without testing, assuming the ratings of critical variants have been established by test.

Dividing responsibility
The second major change implemented by the new industry standard refers to the responsibilities of each party involved in the design, test and implementation of low voltage switchboard assemblies. Unlike BS EN 60439, which stated the OEM or the system manufacturer was solely responsible throughout the testing programme, the new standard divides the responsibilities between the OEM and the assembly manufacturer, or panel builder.

The new standard recognises that several parties may be involved between concept and delivery of a switchboard assembly. The OEM is responsible for the basic design verification. In addition, the assembly manufacturer is meant to oversee the completion of the assembly and routine testing.

For innovators like Boulting Technology, the new BS EN 61439 has brought more freedom and flexibility when designing switchboard assemblies. For example, Boulting Technology has designed and launched the Boulting Power Centre, a range of low voltage switchboards, which are available in 25kA, 50kA, 80kA and 100kA, fault ratings, and up to 6300Amp current ratings.

Although change is never much fun, it’s what technology and industry are all about. If this wasn’t the case, we would all still be using Windows 98 or the indestructible Nokia 5110.